Marshall C Series Packaged Boilers
The Marshall C Series is a robust, high-capacity packaged boiler designed for heavy industrial applications requiring 6 to 25 TPH of steam. Featuring a true three-pass wet back design, it prevents dangerous soot build-up, maintains low flue gas exit temperatures, and guarantees complete combustion. Equipped with advanced Electronic Compound Regulation (ECR) burner technology and a single-element level control system, the Marshall C seamlessly handles fluctuating plant loads while maximizing safety and fuel economy.
Key Technical Specifications:
- Steam Generation Capacity: 6,300 to 25,000 kg/hr (Approx. 13,800 to 55,100 lb/hr).
- Standard Working Pressure: 10.5 / 14.5 / 17.5 kg/cm²(g) (Approx. 150 / 200 / 250 psi).
- Compatible Fuels: High-speed diesel (HSD), light diesel oil (LDO), furnace oil, natural gas, and LPG.
- Guaranteed Efficiency (with HRU): 92% on Oil and 94% on Gas (NCV basis, no tolerance).
- Burner Turndown: 1:3 to 1:5 (FO/Gas).
Related Energy Conservation Tips for Boilers:
- Electronic Compound Regulation (ECR) Burner: Features separate servo motors for air and gas/oil regulating dampers for perfect air-to-fuel ratio control.
- Single Element Level Control System: Standard automated system for highly accurate feedwater management.
- True Three-Pass Wet Back Construction: Fully submerged rear combustion chamber to maximize heat transfer area.
- Stucco Aluminium Cladding: Factory-insulated aesthetics with highly durable aluminum cladding built over the structural frame.
- Advanced Control Panel: Floor-mounted MCC cum ICP panel (IP 54 rated) complete with all alarms, interlocks, and an emergency stop provision.
Variants
A robust 6-25 TPH high-capacity packaged boiler optimized for maximum heat recovery and efficient combustion.
An integrated ready-to-fire boiler house module combining the boiler, feedwater tank, and day oil tank, saving 15% on site job costs and 20% floor space.
Frequently Asked Questions
You can equip the boiler with the Forbes Marshall EffiMax System, an online efficiency monitoring system that continuously tracks direct and indirect efficiency, blowdown, and trim control to ensure optimal real-time performance.
It is built with high thermal inertia—meaning it features a high heat transfer area, high water hold-up, and ample steam space. This acts as a thermal flywheel to deliver dry steam without pressure drops during sudden plant load fluctuations.
The Marshall C offers an excellent burner turndown ratio of 1:3 to 1:5, depending on whether it is firing oil or gas.


EffiMax™ for Oil and Gas Fired Boilers
Boiler Blowdown Control System (BBCS)
Condensate Contamination Detection Systems (CCDS)
Deaerator Head (FMDH)